WCC3.EXE SCREEN DESCRIPTIONS

WCC III Technical Guide

3-162

BINARY GLOBAL SCREEN

BINARY

Global

#:

1

Name

is

GB1

Description: Global Binary 1

On Message #: 1 ON

Mode: 1 Combinatorial

Off Message #: 2 OFF

Value is ON when ANY of the following conditions are met.

W1 is on default false

In Local Set this global defaults to Last Value.

-- Alarm --

Set Condition: None Type 1 Message: 5 Global Alarm

HOME for menu

Binary Global Screen’s WCC III Logical Address is GBXXX, where GB = Global Binary and XXX = Global Binary Address

Binary Global #: ____

Specifi es the global number and its type. Because this is a choice
fi eld, the list of available choices will be displayed at the bottom
of the screen:

<ANALOG, BINARY>

Make your selection by pressing the

<space bar>

once for each

choice until the desired global type has been selected, and then
press

<Enter>

. (If you select a global type that is different than

that currently being displayed, the screen will be rewritten with the
appropriate screen information.)

If you would like to edit a different global, simply position the
cursor to this fi eld by using the cursor positioning (arrow) keys,
enter the desired global number, and press

<Enter>

. The new

screen will automatically appear.

name is ______

Specifi es the name (point address) of this binary global. Any changes
to the global number (above) will be refl ected in this point address
(e.g., BINARY Global #: 28 would show GB28 as the name).

Description: ________________

Specifi es a short message which is displayed on Summary and Data
Entry/Editing Screens
to aid you in remembering points within the
system. You may enter up to 20 characters (control, codes, ALT
codes, and the double quote character are not allowed).

On Message #: ____ Off Message #: ____

Specifi es a pair of message numbers, one for the binary global OFF
state and the second for the binary global ON state. These numbers
are used by the system to reference a textual message which is
displayed in association with this binary global.

Binary Global Screen