WCC3.EXE SCREEN DESCRIPTIONS

WCC III Technical Guide

3-68

SAT TREND LOGGING

The WCC III system SAT III Controller has four trend modes
described below. A SAT cannot trendlog another SAT Analog or
Binary Control Point. The Satellite Controller can only trendlog
its own inputs and output. Week Schedules, Global Binary, Global
Analog, and Optimal Starts can be trendlogged on any Satellite
Controller.

SAT Change of State

A trend logging mode which records any changes of state (i.e.
“OFF” going to “ON” or “ON” going to “OFF”) of a binary value
along with the time and date of the change. Acceptable values are
0, 1, GBXXX, KXh, KXc, WXX, SX, OXX, LXX, CX.

SAT Run Time Total

A trend logging feature which allows the WCC III to accumulate
the amount of time a binary value has been “ON” or “OFF.”
Acceptable values are 0, 1, GBXXX, KXh, KXc, WXX, SX,
OXX, LXX, CX.

SAT Analog Trend

A trend logging mode which records the value of a measured
variable, such as room temperature, at programmed time intervals.
Acceptable values are AX, PX, GAXXX, RXA, RXB.

SAT Analog Peak

A trend logging mode which records the highest and lowest value
of a measured variable along with the time and the date that the
peak occurred. Acceptable values are AX, PX, GAXXX, RXA,
RXB.

WCC III SYSTEM LOGGING

Additional WCC III system long-term trend logging is available
with the WCC3Trendlog.exe program. Any of the following point
addresses can be trend logged:

Satellite Binary Inputs

Satellite Analog Inputs

Satellite Analog Outputs

Satellite Binary Outputs

Satellite Control Outputs H Contact

Satellite Control Outputs C Contact

Satellite Data Register A

Satellite Data Register B

Satellite Run Times

Satellite Logic Switch

WCC Global Analog

WCC Global Binary

WCC Week Schedule

WCC Optimal Start

The WCC3 Trendlog.exe program allows that any of these points
can be charted and graphed and saved. There is an additional option
to save this data fi le as an ODBC database type fi le structure for
viewing in MS Access, Excel, or any other third party database
program that uses ODBC formatting.

WCC III System Logging