Fault state, Reset to default settings – Wavetronix Click 111 (16-channel Contact Closure Eurocard) (CLK-111) - User Guide User Manual

Page 29

Advertising
background image

28

CliCk 111 User GUIde

Because this parameter can also be set by the DIP switches, you may need to ensure that the

DIP switches are set to Software configuration mode; if they are set to Hardware, the front

panel menu will be able to display but not change these settings.

Fault State

The next parameter on the front panel menu label is fault state. To select this parameter,

release the push-button when the yellow, green and red LEDs come on solid.

Note

This parameter can also be changed using the DIP switches or Click Supervisor.

This parameter lets you choose what happens when the device goes into a fault state: wheth-

er that means a call is placed or no call is placed on the channel outputs whose bus has gone

into a fault state.

Level 1 LEDs

Fault State

Level 2 LEDs

Call (default)

No call

LED off
LED on

Cancel and exit menu

Table 17 – Front Panel Menu Fault State Settings

See the earlier Navigating through the Menu and the Menu Operation Example sections for

how to configure this parameter.

Because this parameter can also be set by the DIP switches, you may need to ensure that the

DIP switches are set to Software configuration mode; if they are set to Hardware, the front

panel menu will be able to display but not change these settings.

Reset to Default Settings

The final option that comes up in the menu is Reset to Default Settings. To select this func-

tion, release the mode switch when the red LED starts flashing.

Note

This parameter can only be configured using the DIP switches.

Advertising