Figure 5-4: Check the operation of the 115S-12 module with the AIN Check page.


Test the digital outputs by setting the select-buttons to ON or OFF - this will force the
DO to the selected state.

Digital inputs are reflected in the software by blacking (ON) or greying (OFF) of the
associated label in the Digital Inputs column.

The pulse output count values are also shown. The pulse out target may be set by clicking
the Edit Targets button. Pulses will be produced until the count reaches the target.

The analog inputs can be viewed in decimal or hexadecimal and represents a fraction of
the analog signal, where hex 4000 is 0% and hex C000 is 100%.

In differential configuration, only the value of the first channel in the differential pair
shows the quantity being measured. The second channel of each differential pair should
be ignored.