Serial port baud rate

40203

Serial port parity and stop bit


10. Use the tables below to work out the current communications settings, or write to the

registers using ModScan to change the settings to the desired values. Note that the
module transmission mode should be set to Modbus RTU.

Modbus address 40201, serial port transmission mode:

Setting

Register Value

Modbus RTU

0x0101

Modbus ASCII, 8 data bits

0x0201

Modbus ASCII, 7 data bits

0x0202


Modbus address 40202, serial port baud rate:

Setting

Register Value

1200

0x000C

2400

0x0018

4800

0x0030

9600

0x0060

14400

0x0090

19200

0x00C0

28800

0x0120

38400

0x0180

57600

0x0240

76800

0x0300

115200

0x0480

Modbus address 40203, serial port parity and stop bit:

Parity Setting

Register’s High Byte Value

None

0x00

Odd

0x11

Even

0x22

Stop-bit Setting

Register’s Low Byte Value

1 stop bit

0x11

2 stop bits

0x22


11. Once the new comms setting are correct, be sure to change the address switches back

to a non-zero setting for normal operation.