115S Serial I/O Module
User Manual
man_115S_1.14.docx
Page 51
Data
Modbus I/O Type
Modbus
Addresses
Analog outputs 2
Holding registers
40002
Analog outputs 3
Holding registers
40003
Analog outputs 4
Holding registers
40004
Analog outputs 5
Holding registers
40005
Analog outputs 6
Holding registers
40006
Analog outputs 7
Holding registers
40007
Analog outputs 8
Holding registers
40008
Module supply voltage
*
Input registers
30033
Analog supply voltage (28V)
+
Input registers
30034
Serial port transmission mode
Input registers
30201
Serial port baud rate
Input registers
30202
Serial port parity and stop bit
Input registers
30203
Modbus Comms Fail Timeout
!
Input registers
30204
ELPRO ACK Timeout
!
Input registers
30205
Module Firmware version
%
Input Register
30801
*
0x4000 = 8V; 0xC000 = 40V (Firmware earlier than 2.00 is 0x4000 = 8V; 0xC000 = 16V
+
0x4000 =12V; 0xC000 = 36V
!
Timeout values in 32mSec increments
%
0x0204 = Ver 2.04