Test the digital outputs by setting the select-buttons to ON or OFF - this will force the
DO to the selected state.

Digital inputs are reflected in the software by blacking (ON) or greying (OFF) of the
associated label in the Digital Inputs column.

The pulse output count values are also shown. The pulse out target may be set by clicking
the Edit Targets button. Pulses will be produced until the count reaches the target.

The analog outputs can be viewed in decimal or hexadecimal and represents a fraction of
the analog signal, where hex 4000 is 0% and hex C000 is 100%.

The analog output values can be set by the user for testing, and the output signal
measured to confirm the analog operation. If you are using hexadecimal values (which is
the easiest) ensure the $ symbol precedes the value to denote a hex number.