Westermo RM-115S User Manual

Page 49

Advertising
background image

115S Serial I/O Module

User Manual

man_115S_1.14.docx

Page 49

Data

Modbus I/O Type

Modbus

Addresses

Analog inputs 1

Input registers

30001

Analog inputs 2

Input registers

30002

Analog inputs 3

Input registers

30003

Analog inputs 4

Input registers

30004

Analog inputs 5

Input registers

30005

Analog inputs 6

Input registers

30006

Analog inputs 7

Input registers

30007

Analog inputs 8

Input registers

30008

Module supply voltage

*

Input registers

30033

Analog supply voltage (24V)

+

Input registers

30034

Serial port transmission mode

Input registers

30201

Serial port baud rate

Input registers

30202

Serial port parity and stop bit

Input registers

30203

Modbus Comms Fail Timeout

!

Input registers

30204

ELPRO ACK Timeout

!

Input registers

30205

Module Firmware version

%

Input Register

30801

*

0x4000 = 8V; 0xC000 = 40V (Firmware earlier than 2.00 is 0x4000 = 8V; 0xC000 = 16V

+

0x4000 =12V; 0xC000 = 36V

!

Timeout values in 32mSec increments

%

0x0204 = Ver 2.04

Note: If using Differential Voltage or Current inputs, only the odd inputs should be
used, i.e. AIN1 for the first input, AIN3 for the second, AIN5 for the third and AIN7
for the fourth.