Westermo RM-115S User Manual

Page 55

Advertising
background image

115S Serial I/O Module

User Manual

man_115S_1.14.docx

Page 55

Appendix D. Specifications


EMC Approval

EN 55024:1998

EN 61000-3-2: 2002
EN 61000-3-3: 2002

EN 55022: 1998

FCC Part 15

Operating temperature
range

-40 to +60 deg C

Power supply

10.8 – 30.0 VDC

13.8V / 24VDC nom

Model Dependent. Check

rear label for actual

operating voltages

Supply current (idle 13.8V)

-11

-12

-13

100mA
100mA
120mA

Supply current for I/O

per digital input

per digital output

per analog input

per analog output

13mA
13mA
50mA
50mA





If using 24V loop supply

Loop supply

24V nominal *

* Loop supply will follow
115S-xx power supply
voltage above 24V input.

Loop supply max current

115S-12 : 270mA

115S-13 : 160mA

RS232 port

Modbus protocol

RS485 port

Modbus protocol

ELPRO E-Series protocol

Modbus protocol

Transmission modes

Modbus ASCII 8 data bits

Modbus ASCII 7 data

bits**

Modbus RTU

** If no parity, use 2 stop
bits. If using parity, use 1
stop bit.

Baud rates

1200; 2400; 4800; 9600;

14,400; 19,200; 28,800;
38,400; 57,600; 76,800;

115,200

Parity

Odd, even, none

Stop bits

1, 2

Slave address

Modbus = 01-99

Elpro = 96 - 127. Note:
Each module requires 3
addresses meaning the
maximum number of serial
modules per radio is 10.

Advertising