5

Installation

5.1

Safety during Installation

Danger to life from electric shock due to live voltage

High voltages are present in the live components of the product. Touching live components results in death or serious
injury due to electric shock.

• Wear suitable personal protective equipment for all work on the product.

• Do not touch any live components.

• Observe all warning messages on the product and in the documentation.

• Observe all safety information of the module manufacturer.

• After switching off the inverter, wait at least 15 minutes before opening it to allow the capacitors to discharge

completely (see Section 6.2, page 36).

Danger to life from electric shock due to live DC cables

DC cables connected to PV modules that are exposed to sunlight carry live voltage. Touching live cables results in
death or serious injury due to electric shock.

• Prior to connecting the DC cables, ensure that the DC cables are voltage-free.

• Wear suitable personal protective equipment for all work on the device.

Danger to life from electric shock due to ground fault

If a ground fault has occurred, parts of the PV power plant that are supposedly grounded may in fact be live.
Touching incorrectly grounded parts of the PV power plant results in death or serious injuries from electric shock.

• Before working on the PV power plant, ensure that no ground fault is present.

• Wear suitable personal protective equipment for all work on the device.

Danger to life from electric shock when entering the PV field

Ground-fault monitoring does not provide protection from personal injury. PV modules which are grounded with
ground-fault monitoring discharge voltage to ground. Entering the PV field can result in lethal electric shocks.

• Ensure that the insulation resistance of the PV field exceeds the minimum value. The minimum value of the

insulation resistance is: 1 kΩ.

• Before entering the PV field, switch the PV modules to insulated operation.

• Configure the PV power plant as a closed electrical operating area.

5 Installation

SMA Solar Technology AG

Operating Manual

21