Danger to life due to electric shock or electric arc if live components are touched

• Switch off the inverter and wait at least 15 minutes before opening it to allow the capacitors to discharge

completely.

• Disconnect the inverter (see Section 6, page 36).

Disassembling the protective covers

Requirements:

☐ The panels must be disassembled (see Section 7.2.1, page 40).

Procedure:

• Disassemble the protective covers.

Mounting the protective covers

1. Tighten all protective covers (torque: 5 Nm).

2. Ensure that the protective covers are firmly in place.

7.2.3

Disassembling and Mounting the Ventilation Grids

Disassembling the ventilation grids

1. Release the screws of the right-hand ventilation grid.

2. Pull the lower side of the right-hand ventilation grid forwards to

remove it.

3. Release the screws of the left-hand ventilation grid.

7 Periodic Actions