DC Input

Maximum DC Power

560 kW

Minimum input voltage / maximum input voltage

400 V to 1,000 V

Minimum MPP voltage

430 V

MPP voltage range at +25 C

449 V to 850 V

MPP voltage range at +50 C

430 V to 850 V

MPP voltage range at +25°C and 60 Hz

449 V to 850 V

MPP voltage range at +50°C and 60 Hz

436 V to 850 V

Rated input voltage

449 V

Maximum input current

1,250 A

Maximum short-circuit current

2,500 A

Maximum reverse current

2,300 A

Number of independent MPP inputs

1

Number of DC inputs

9

AC Output

Rated power at +25°C

550 kVA

Rated power at +50°C

500 kVA

Nominal AC voltage

270 V

Nominal AC voltage range

243 V to 310 V

AC power frequency

50 Hz / 60 Hz

AC power frequency range

47 Hz to 63 Hz

Rated frequency

50 Hz

Rated grid voltage

270 V

Maximum total harmonic distortion

0.03

Maximum AC current

1,176 A

1,238 A*

Maximum overcurrent protection at output

50,000 A

Maximum residual current at the AC output

3,500 A

Power factor at rated power

1

Displacement power factor cos φ

0.9 overexcited to 0.9 underexcited