5.4.3

Connecting the DC Cables to the Connection Brackets

Figure 7: Connection area for DC fuses (example)

Position

Designation

A

Connection area DC‒

B

Connection area DC+

C

DC connection bracket with dimensions

Terminal lug requirements:

☐ Use tin-plated terminal lugs only.

☐ For the connection, only the supplied screws, washers and nuts must be used.

☐ The terminal lugs must be designed according to the temperature. Temperature: +95°C

☐ The width of the terminal lugs must exceed the washer diameter. Washer diameter: 32 mm. This will ensure that

the defined torques are effective over the whole surface.

Cable requirements:

☐ No more than two cables must be connected to each DC terminal.

☐ Use copper or aluminum cables only.

☐ Maximum cable cross-section: 400 mm².