2 sunny central 630cp xt, Sunny central 630cp xt – SMA SC 500CP XT Installation User Manual

Page 54

Advertising
background image

8.2

Sunny Central 630CP XT

DC Input

Maximum DC Power

713 kW

Minimum input voltage / maximum input voltage

460 V to 1,000 V

Minimum MPP voltage

500 V

MPP voltage range at +25 C

529 V to 850 V

MPP voltage range at +50 C

500 V to 850 V

MPP voltage range at +25°C and 60 Hz

529 V to 850 V

MPP voltage range at +50°C and 60 Hz

505 V to 850 V

Rated input voltage

529 V

Maximum input current

1,350 A

Maximum short-circuit current

2,500 A

Maximum reverse current

2,300 A

Number of independent MPP inputs

1

Number of DC inputs

9

AC Output

Rated power at +25°C

700 kVA

Rated power at +50°C

630 kVA

Nominal AC voltage

315 V

Nominal AC voltage range

284 V to 362 V

AC power frequency

50 Hz / 60 Hz

AC power frequency range

47 Hz to 63 Hz

Rated frequency

50 Hz

Rated grid voltage

315 V

Maximum total harmonic distortion

0.03

Maximum AC current

1,283 A

1,350 A*

Maximum residual current at the AC output

3,500 A

Maximum overcurrent protection at output

50,000 A

Power factor at rated power

1

Displacement power factor cos φ

0.9 overexcited to 0.9 underexcited

Feed-in phases

3