SMA SC 500CP XT Installation User Manual

Page 59

Advertising
background image

AC Output

Connection phases

3

Inrush current of the internal power supply

48 A (100 ms)

Efficiency

Maximum efficiency

98.6%

European weighted efficiency

98.4%

CEC weighted efficiency

98.5%

Protective Devices

DC overvoltage protection

Type I

Lightning protection as per IEC 62305-1

Lightning protection level III

Surge arrester for auxiliary power supply

Yes

Protection class in accordance with IEC 62103

I

Overvoltage category as per IEC 60664-1

III

General Data

Width x height x depth

2,562 mm x 2,272 mm x 956 mm

Weight

1,900 kg

Operating temperature range

−25°C to +62°C

Operating temperature range for low-temperature option

−40°C to +62°C

Noise emission at a distance of 10 m

60 db(A)

Self-consumption in operation

< 1,950 W

Standby consumption

< 100 W

External supply voltage

230 V / 400 V (3/N/PE), 50 Hz / 60 Hz

Degree of protection of electronics

IP54

Degree of protection of the connection area

IP43

Maximum permissible value for relative humidity (non-
condensing)

15 % … 95 %

Maximum operating altitude above mean sea level

2,000 m

Maximum operating altitude above MSL for option "In-
stallation at high altitudes"

4,000 m

Fresh air consumption

3,000 m³/h

8 Technical Data

SMA Solar Technology AG

Operating Manual

59

SCCPXT-IA-E4-en-44

Advertising