2 minimum clearances in electrical equipment rooms, Minimum clearances in electrical equipment rooms – SMA SC 500CP XT Installation User Manual

Page 73

Advertising
background image

Minimum clearances between two inverters and transformer

Version 2: Front to front

Figure 24: Minimum clearances between two inverters and transformer

Position

Designation

A

Inverter 1

B

Inverter 2

C

MV transformer and medium-voltage switchgear

D

Cable route between inverter and MV transformer

Recommended clearances for the facilitation of service work

In order to facilitate service work, minimum clearances to the rear and sides of 1,000 mm are recommended. If you
are using a service tent during installation and service work, maintain 5,000 mm clearance to the inverter.

9.1.6.2

Minimum Clearances in Electrical Equipment Rooms

Damage due to intake of exhaust air or blocked exhaust air outlets

The supply air is intended to cool the inverter components. Failure to observe the specified minimum clearances can
result in warm exhaust air from the inverter being drawn in. This increases the risk of a thermal short circuit. Property
damage due to yield loss and damage to the components may result.

• Ensure that no exhaust air can be drawn in through the air inlets.

• Ensure that it is not possible for exhaust air to be drawn into the air intake of other devices.

• Make sure that the exhaust air vents are not obstructed.

• Make sure that the exhaust air vents are accessible for cleaning at all times.

• Ensure that the minimum clearances are complied with.

9 Appendix

SMA Solar Technology AG

Operating Manual

73

SCCPXT-IA-E4-en-44