17  Technical Data

Installation Manual

SCCP-US-IA-US_en-41

105

Ambient Conditions

17.8 Sunny Central 850CP-US/CA

Input Data

Output Data

Power Consumption

CEC-eta

98.5%

Enclosure rating outdoor

Type 3R

Enclosure rating indoor

Type 1

Operating temperature range

− 13°F to 122°F ( − 25°C to +50°C)

Maximum altitude above mean sea level, MSL

6,562 ft. (2,000 m)

Supply air flow and quality

1766 SCFM (3,000 m

3

/h), Class 4S2

MPP voltage range

620 V

DC

to 820 V

DC

Maximum DC voltage

820 V

Maximum DC current

1,600 A

DC

Max. array short circuit current

2,596 A

DC

Number of DC inputs*

* Only in the inverter option with DC fuses single phase

9

DC overvoltage category

II

Continuous AC power at +122°F (+50°C)

850 kVA

Continuous AC power at +104°F (+40°C)

884 kVA

Continuous AC power at +77°F (+25°C)

935 kVA

AC current at +122°F (+50°C)

1,271 A

AC

AC current at +104°F (+40°C)

1,322 A

AC

AC current at +77°F (+25°C)

1,399 A

AC

Nominal AC voltage ± 10%

386 V

AC

Nominal power frequency

60 Hz [50 Hz]

Power frequency range

59.3 Hz to 60.5 Hz [49.3 Hz to 50.5 Hz]

Power factor cos φ

0.8 to 1

Current THD

< 5% (with respect to IEEE 1547)

AC overvoltage category

IV

Self-consumption in operation

< 1,800 W

Standby consumption

< 150 W

Control supply voltage

See nameplate in the connection area of the control circuit

Advertising