2 safety, 1 intended use – SMA SC 500CP-US User Manual

Page 11

Advertising
background image

SMA America, LLC

2  Safety

Installation Manual

SCCP-US-IA-US_en-41

11

2 Safety

In this section, you will find general safety precautions which you must observe whenever working on the Sunny Central

inverter. Pay special attention to these sections to avoid personal injury and property damage.

2.1 Intended Use

The inverter converts the direct current generated in the PV modules into grid-compliant alternating current. An external

MV transformer fitted downstream feeds the alternating current generated into the utility grid.
The inverter is designed for indoor and outdoor installation. The inverter is only licensed for use with a suitable transformer

and providing that the maximum permissible DC input voltage and the permitted ambient conditions are complied with

(see Section 17 "Technical Data", page 98). The transformer must be designed for voltages that arise during pulsed

mode of the inverter.
The inverter has been evaluated by UL for compliance with UL 1741 / IEEE 1547 requirements at the inverter’s terminals

on the local area side of an interconnection transformer for all IEEE 1547 tests other than for Unintentional Islanding. It

has additionally been evaluated for selected tests for use with UL Recognized Component low-voltage transformers as

noted in the table below:

The inverter has not been evaluated for exporting current into low-voltage electrical power system (EPS) with local loads

present, and must connect to the medium voltage EPS via an externally-provided medium-voltage transformer.
The external medium-voltage transformer shall provide isolated primary and secondary windings rated for the output

voltage and kVA rating of the inverter. The medium-voltage transformer shall be located between the output of the inverter

and the medium-voltage utility power connection.
The Authority Having Jurisdiction (AHJ) must consider the effect of the medium-voltage transformer provided in the field

with respect to electrical ratings, impedance, and the resultant effects on the utility interconnection performance of the

inverter, with respect to the ratings and impedance of the transformer selected.
The inverter has not been evaluated for an installation of multiple inverters connected to one transformer. The Authority

Having Jurisdiction shall determine if any additional evaluation is necessary of such a system.
The inverter can optionally be equipped with an AC power switch for "branch circuit protection". This AC circuit breaker

simultaneously acts as the AC Disconnect in accordance with NEC ANSI/NFPA 70 and CEC. For inverters without an

AC circuit breaker, "branch circuit protection" and an AC Disconnect must be implemented by the installer. Further

information is provided in section 3.1.
The inverter with an integrated AC Disconnect can be optionally ordered with an integrated DC Switch in order to be

able to disconnect the inverter from the PV array. Both devices are designed to be used with a lockout device to secure

the inverter against reconnection during service. If the inverter does not have an integrated DC Switch, an external DC

Disconnect must be installed in accordance with NEC ANSI/NFPA 70 and CEC, in order to be able to disconnect the

inverter from the PV array.

Test

Manufacturer Model

Electrical Ratings

Unintentional Islanding Test

J. Schneider

DLGX

1000F-1016TO1001

Primary 289 V

Secondary 480 V, 1,000 kVA

Synchronization, Harmonics,

and Open Phase

J. Schneider

DLGX

1250F-1001TO1001

Primary 480 V / 1,500 A

Secondary 480 V / 1,500 A, 1,250 kVA

:$51,1*

If the unit is not provided with a GFDI or insulation monitoring device, this inverter must be used with an

external GFDI as required by the Article 690 of the National Electrical Code

®

for the installation location or

an external insulation monitoring device according to UL 1741.

Advertising
This manual is related to the following products: