2 requirements for the mounting location, 1 ambient conditions, 2 supply air and exhaust air – SMA SC 500CP-US User Manual

Page 33

Advertising
background image

SMA America, LLC

6  Preparation for Installation

Installation Manual

SCCP-US-IA-US_en-41

33

6.2 Requirements for the Mounting Location

This section describes which requirements must be met at the mounting location of the inverter. The conditions specified

here apply equally for each installation option. Observe this section and make sure that the requirements are met prior

to preparing the mounting location for the inverter.

6.2.1 Ambient Conditions

The following ambient conditions must be maintained under all circumstances to ensure the optimum and safe operation

of the inverter.

☐ The mounting location must be freely accessible at all times.
☐ The ambient temperature must be within the operating temperature range.
☐ For further information on the ambient conditions, (see Section 17 "Technical Data", page 98).

For further information on the installation, see "Installation requirements for Sunny Central CP-US", which can be

downloaded in the download area at www.SMA-America.com or www.SMA-Solar.com.

6.2.2 Supply Air and Exhaust Air

The innovative OptiCool cooling concept makes it possible to operate inverters at full nominal power at ambient

temperatures of up to +122°F (+50°C).
At temperatures exceeding +122 °F (+50 °C), the inverter continues feeding in but reduces feed-in power to protect the

PV system.
The cooling air is drawn in through the inverter roof and is blown out

again through the slits at the rear of the inverter.
The illustration on the right shows the principle of the air circulation within

the inverter.
The inverter needs 1766 SCFM (3,000 m

3

/h) of fresh air, which the

inverter draws in through the ventilation grids in the front. The fresh air

must meet the 4S2 classification.
You can install the inverter in a chemically active environment. The

inverter is protected against salt spray in accordance with

EN 60721-3-4 class 4C2. You will find the required air qualities in the

following table.

/05*$&

Damage to the inverter due to dust or moisture penetration
Dust intrusion or moisture penetration can damage the inverter or impair the functionality of the inverter.

• Do not open the inverter during rainfall or humidity of more than 95%.
• Only open the inverter when the environment is dry and free of dust.
• Only use rainproof, wet-room suitable conduits that comply with UL 514B for the connection to the switch cabinet.

Advertising
This manual is related to the following products: