SMA SC 500CP-US User Manual

Page 70

Advertising
background image

10  DC Connection

SMA America, LLC

70

SCCP-US-IA-US_en-41

Installation Manual

Procedure:

1. Strip the DC cable insulation appropriately for the terminal lugs to be used.
2. Fit terminal lugs to the DC cables.
3. Clean the contact surfaces using a clean cloth and ethanol cleaning agent and do not touch the contact surfaces

after cleaning.

4. Connect the DC cables with the specified torque in accordance with the circuit diagram. Only use the screws,

washers and nuts included in the scope of delivery.

5. Secure the DC cables on the cable support rail.

Type of terminal lug

Torque

Copper terminal lug on copper bus bar

44.5 ft.-lbs. (60 Nm)

Tin-plated aluminum terminal lug on copper bus bar 27.5 ft.-lbs. (37 Nm)
Tin-plated aluminum terminal lug on tin-plated

aluminum bus bar

27.5 ft.-lbs. (37 Nm)

Copper terminal lug on tin-plated aluminum bus bar 27.5 ft.-lbs. (37 Nm)

Advertising
This manual is related to the following products: