10 integrated ac disconnect – SMA SC 500CP-US User Manual

Page 107

Advertising
background image

SMA America, LLC

17  Technical Data

Installation Manual

SCCP-US-IA-US_en-41

107

Power Consumption

Dimensions and Weight

Efficiency

Ambient Conditions

17.10 Integrated AC Disconnect

AC Disconnect Ratings

AC overvoltage category

IV

Self-consumption in operation

< 1,800 W

Standby consumption

< 150 W

Control supply voltage

See nameplate in the connection area of the control circuit

Width x height x depth

8 ft. 4.87 in x 7 ft. 5.45 in x 3 ft. 1.64 in.

(2,562 mm x 2,272 mm x 956 mm)

Weight

4,123 lb (1,870 kg)

Maximum efficiency

98.6%

CEC-eta

98.5%

Enclosure rating outdoor

Type 3R

Enclosure rating indoor

Type 1

Operating temperature range

− 13°F to 122°F ( − 25°C to +50°C)

Maximum altitude above mean sea level, MSL

6,562 ft. (2,000 m)

Supply air flow and quality

1766 SCFM (3,000 m

3

/h), Class 4S2

Compliance Standard

UL 1066

Frame Size

1600 A

Rated maximum voltage

635 V

Rated short-circuit current

42 kA

Rated short-time current

42 kA

Rated frequency

50 Hz - 60 Hz

Make time (max)

80 ms

Break time (I<ST current)(max)

70 ms

Break time (I>ST current)(max)

30 ms