6  Preparation for Installation

SMA America, LLC

40

SCCP-US-IA-US_en-41

Installation Manual

Cable Arrangement for AC Cables Shorter than 6.5 ft. (2 m)

Arrange the cables as shown in the following figure for each number of cables having a length shorter than 6.5 ft. (2 m).

The description is provided as an example for an arrangement with four cables per line conductor. The distance between

the cables should be twice the diameter of a single cable.

Figure 20: AC cable arrangement 1

Cable Arrangement for AC Cables Longer than 6.5 ft. (2 m)

Arrange all cables with a length of over 6.5 ft. (2 m) as shown in the following figure. The description is provided as an

example for an arrangement with four cables per line conductor.
For AC cable arrangement 1: The distance between the cables should be twice the diameter of a single cable.

Figure 21: AC cable arrangement 2

Figure 22: AC cable arrangement 3

Requirement:

☐ The AC cables must be bundled in the three-phase system.
☐ Between the medium-voltage transformer and the inverter there must be three separate cable routes for the AC

cables, e.g. cable channels.

Procedure:

• Lay one A, B and C line conductor in each cable route. Ensure the distance between the cable bundles is at least

double that of the diameter of a cable. This prevents current imbalances.*

6

If possible: AC cable arrangement 3
Otherwise: AC cable arrangement 1

* For further information, see the Technical Information "Cable Set ‒ Requirements for and Laying of Cables between SUNNY CENTRAL CP

and TRANSFORMER COMPACT STATION"

Number of cables per

line conductor

AC cable arrangement