12  Cable Connection of External Devices in the Interface Cabinet

SMA America, LLC

78

SCCP-US-IA-US_en-41

Installation Manual

12.2 Cable Requirements

☐ Only use copper cables.
☐ The cables for the setpoints, remote shutdown and external fast stop must be shielded.
☐ The data cables must be laid and attached separately from the power cables in accordance with 300.3(C)(2) NEC

2011.

The following table shows the requirements of the field wiring conductors:

12.3 Switching off the Circuit Breaker

1. Switch off the voltage supply.

• If the voltage is supplied externally, switch off the circuit

breaker of the external voltage supply.

or

• If the voltage supply is supplied internally, switch off the circuit

breaker of the internal supply voltage.

I

Sealing plate

K

External voltage supply terminal

L

External fast stop terminal

M

Circuit breaker of the external voltage supply*

* Optional

Terminal

Cable size

Cable type

=SC‒X210

12 AWG (2.5 mm²) minimum

+140°F (+60°C) minimum, copper

wire

=SC‒X725 /

=SC‒X750 … =SC‒X757;
=SC‒X760;
=SC‒X770;
=SC‒X780

14 AWG (1.5 mm²) minimum

+194°F (+90°C) minimum, copper

wire

Position

Description