17.1 Measurement Accuracy

The inverter is not equipped with a calibrated meter. The display values may deviate from the actual values and must not

be used as a basis for invoicing. The inverter’s measured values are required for the system management and to control

the current to be fed to the grid.

Deviation:

Voltage measurement: +/– 8.5 V
Frequency measurement: +/– 0.06 Hz
Disconnect time: +/–4.5%

17.2 Sunny Central 500CP-US/CA

Input Data

Output Data

Power Consumption

MPP voltage range

430 V

DC

to 820 V

DC

Maximum DC voltage

1,000 V

DC

Maximum DC current

1,600 A

DC

Max. array short circuit current

2,596 A

DC

Number of DC inputs*

* Only in the inverter option with DC fuses single phase

9

DC overvoltage category

II

Continuous AC power at +122°F (+50°C)

500 kVA

Continuous AC power at +104°F (+40°C)

520 kVA

Continuous AC power at +77°F (+25°C)

550 kVA

AC current at +122°F (+50°C)

1,069 A

AC

AC current at +104°F (+40°C)

1,112 A

AC

AC current at +77°F (+25°C)

1,167 A

AC

Nominal AC voltage ± 10%

270 V

AC

Nominal power frequency

60 Hz [50 Hz]

Power frequency range

59.3 Hz to 60.5 Hz [49.3 Hz to 50.5 Hz]

Power factor cos φ

0.8 to 1

Current total harmonic distortion

< 5% (with respect to IEEE 1547)

AC overvoltage category

IV

Self-consumption in operation

< 1,800 W

Standby consumption

< 150 W

Control supply voltage

See nameplate in the connection area of the control circuit