16 commissioning, 1 commissioning the inverter – SMA SC 500CP-US User Manual

Page 92

Advertising
background image

16  Commissioning

SMA America, LLC

92

SCCP-US-IA-US_en-41

Installation Manual

16 Commissioning

16.1 Commissioning the Inverter

:$51,1*

Fire hazard due to faulty connection
If the cables and connections are incorrectly connected, the cables and connections can overheat and catch fire. This

may result in death or serious injury.

• Before commissioning, make sure that all cables and connections are correctly connected.
• Switch off all switch elements before the test:

– Switch the inverter to Stop using the key switch.
– Remove the fuses.
– Switch off the internal main switches and circuit breakers.

Statutory warranty or guarantee claims
Statutory warranty or guarantee claims can only be asserted if the initial start-up was carried out by SMA or if the

fully completed and signed "Commissioning Report for Sunny Central Plants" is available at SMA.

Unused remote shutdown

• If the remote shutdown is not used, set the parameter ExtStrStpEna to Off during commissioning (see the

Sunny Central operating manual).

Inverter without transformer protection

• If you are not using the transformer protection option, set the ExtTrfErrEna parameter to Off after

commissioning (see the Sunny Central operating manual).

Connecting and disconnecting the AC voltage of the medium-voltage transformer
Only a duly authorized person trained in electrical safety is allowed to connect and disconnect the AC voltage of

the medium-voltage transformer.

Procedure

See

1.

Check the inverter cabling.

Section 16.2, page 93

2.

Insert the DC fuses.

Section 13, page 84

3.

Mount the protective covers.

Section 16.3, page 93

4.

If applicable, commission the DC sub-distribution.

DC sub-distribution

documentation

5.

If applicable, commission the DC main distribution.

DC main distribution

documentation

6.

Check the DC voltages.

Section 16.4.1, page 94

7.

Have a duly authorized person trained in electrical switching connect the

AC voltage of the medium-voltage transformer externally.

Medium-voltage transformer

documentation

8.

Check the AC line voltage.

Section 16.4.2, page 94

9.

Check the internal power supply.

Section 16.4.3, page 94

10.

Switch the voltage supply on.

Section 16.5, page 95

11.

If applicable, switch on the AC Disconnect.

Section 16.6, page 96

Advertising