2 position of the mounting holes on the inverter, 3 drilling mounting holes in the foundation – SMA SC 500CP-US User Manual

Page 42

Advertising
background image

6  Preparation for Installation

SMA America, LLC

42

SCCP-US-IA-US_en-41

Installation Manual

6.3.2 Position of the Mounting Holes on the Inverter

There are six mounting holes in the base area of the inverter for fixing it to the foundation. In addition, you can use the

two outer mounting brackets.

Figure 24: Position of the mounting holes on the inverter

The diameter of the mounting holes is

5

8

in. (16 mm).

6.3.3 Drilling Mounting Holes in the Foundation

1. Measure the distance for the drill holes.
2. Mark the positions of the drill holes.
3. Drill mounting holes at the positions marked in the foundation (diameter 0.62 in. (16 mm)).

Clearance between

Clearance

Mounting holes 1 and 2

53.03 in. (1,347 mm)

Mounting holes 2 and 3

39.37 in. (1,000 mm)

Mounting holes 3 and 4

31.69 in. (805 mm)

Mounting holes 4 and 5

39.37 in. (1,000 mm)

Mounting holes 5 and 6

53.03 in. (1,347 mm)

Mounting holes 1 and 6

31.69 in. (805 mm)

Outer mounting holes

31.30 in. (795 mm)

Advertising
This manual is related to the following products: