16  Commissioning

Installation Manual

SCCP-US-IA-US_en-41

93

16.2 Checking the Inverter Cabling

1. Ensure that all connections are executed in accordance with the circuit diagram.
2. Check that the AC, DC, and protective conductor cables are securely connected.
3. Ensure that there is equipotential bonding between the inverter and the mounting location.
4. Ensure that all connections in the interface cabinet are securely in place.
5. Attach all cables in the connection area to the cable support rail using cable ties.

16.3 Mounting the Protective Covers

Before you switch on the inverter, all protective covers and panels must be mounted. ]

Figure 46: Position of the protective covers in the inverter

Procedure:

• Screw all protective covers into place. Tighten to the torque specified:

12.

Mount the panels.

Section 16.7, page 96

13.

Switch on the inverter.

Section 16.8, page 97

Position

Description

A

Protective cover

Protective covers

Torque

In the interface cabinet

In the connection area

7.4 ft.-lbs (10 Nm)

All others

2.2 ft.-lbs. (3 Nm)

Procedure

See