3  Product Description

SMA America, LLC

22

SCCP-US-IA-US_en-41

Installation Manual

Sunny Central Inverter with Integrated AC Disconnect and External DC Disconnect

Figure 4: Principle of a grid-tie PV plant with an external DC Disconnect and a inverter with integrated AC Disconnect

Sunny Central Inverter with External AC Disconnect and External DC Disconnect

As an option, the AC circuit breaker can be mounted externally.

Figure 5: Principle of a grid-tie PV plant with a Sunny Central inverter and external AC / DC Disconnect Unit

Position

Description

A

PV array

B

String Combiner Box

C

Inverter with Integrated AC Disconnect

D

DC Disconnect Unit

E

External transformer

F

Utility grid

Circuit breaker
The unit is provided with a UL listed circuit breaker on the output rated 1,600 A for branch circuit protection. If the

circuit breaker shall be located externally to secure the AC path, you have to use the same type of circuit breaker

(ABB Emax E2B-A with 42 kA rated short-circuit current, ABB Emax E2N-A with 65 kA rated short-circuit current or

ABB Emax E2H-A with 85 kA rated short-circuit current and 1,600 A continuous current rating each).

Position

Description

A

PV modules