SMA America, LLC

10  DC Connection

Installation Manual

SCCP-US-IA-US_en-41

69

Overview of the Connection Assembly

Figure 41: Assembly of the connection with two-hole terminal lugs

Requirements:

☐ The grounding type of the PV modules must be known.
☐ The cable requirements must be complied with (see Section 10.2 "Requirements for the Cables and Cable

Connection", page 60).

Additionally required mounting material (not included in the scope of delivery):

☐ Clean cloth
☐ Ethanol cleaning agent

Disconnection on the DC side
The DC main distributions and DC sub-distributions should be equipped with circuit breakers. Circuit breakers enable

trouble-free DC-side disconnection of the inverter.

Position

Description

A

Nut M12

B

Spring washer

C

Fender washer

D

Two-hole terminal lug

E

Busbar

F

Screw M12