2 sunny central string-monitor controller, Sunny central string-monitor controller, H-on – SMA SC 500HE-20 User Manual

Page 100: Cab1, Cab2

Advertising
background image

12  Parameters

SMA Solar Technology AG

100

SCxxxHE-20-BE-BEN111210

Operating Manual

12.2 Sunny Central String-Monitor Controller

ExlStrStpEna

*

Enable external
shutdown signal/
remote shutdown

Off

Deactivated

Off

On

Activated

ExlTrfErrEna

*

Enable hermetic
protection of medium
voltage transformer

Off

Deactivated

On

On

Activated

These parameters are only visible after the installer password has been entered.

** 

These parameters can only be changed after the installer password has been entered.

Name

Description

Value/Range

Explanation

Default

value

TolGr1

*

Currents from group
1 deviate from mean
value
Parameter exists for
all 6 groups

5% … 100%

13%

MoniTmGr1On

*

Time when group 1
monitoring begins
Parameter exists for
all 8 groups

7:00 a.m. …

7:00 p.m.

10:00 a.m.

MoniTmGr1Off

*

Time when group 1
monitoring stops
Parameter exists for
all 6 groups

7:00 a.m. …

7:00 p.m.

3:00 p.m.

MoniTmGrAllOn

*

Time when monitoring
of all groups begins

7:00 a.m. …

7:00 p.m.

10:00 a.m.

MoniTmGrAllOff

*

Time when monitoring
of all groups stops

7:00 a.m. …

7:00 p.m.

3:00 p.m.

Ackn

Acknowledge error in
Sunny Central String-
Monitor Controller

---

---

Ackn

Select parameter to
acknowledge an
error

Name

Description

Value/Range

Explanation

Default

value

Advertising