6  Setpoint for Active Power and Reactive Power

Operating Manual

SCxxxHE-20-BE-BEN111210

45

If the power frequency exceeds a user-defined limit "P-HzStr" as shown in point A, the Sunny Central
will save the current feed-in power P

cur

. The reduced feed-in power is calculated based on this saved

value. The reduction of the feed-in power is defined through the "P-WGra" parameter. This parameter
indicates by which percentage of the saved power P

cur

output will be reduced per Hz if the power

frequency continues to rise.
If the power frequency decreases again as shown in point B, the last reached feed-in power will
remain valid. Only if the power falls below the user-defined limit "P-HzStop" as shown in point C, the
fed-in power may be increased again. The saved value "P

cur

" will be rendered invalid.

If the power frequency exceed the grid limit, the Sunny Central will shut down and switch over to the
"Grid monitoring" operating state. The Sunny Central will remain in the "Grid monitoring" operating
state until all feed-in conditions are fulfilled again.
Calculating the power limit
Formula: P

lim

= P

cur

– ( (f

grid

– P-HzStr) * P-WGra * P

cur

)

6.1.10 Active Power Limitation Procedure Depending on Power

Frequency and Associated Parameter Setting

1. Make sure the inverter is in the "Stop" operating state.
2. Access the SC-COM interface.
3. Enter your password in the appropriate field on the homepage and press [Login].
4. On the SC-COM interface, set the "WCtlHzMod" parameter to On (see section 5.2 "Changing

Parameters", page 34).

5. Change used parameters.

P

lim

Power limit

P

cur

Current power

f

grid

Power frequency

P-HzStr

Selected frequency limit at which
the feed-in power will be reduced

P-WGra

Gradient for reducing active
power

Example:
A Sunny Central with 500 kW is feeding 350 kW (P

cur

) into the power distribution grid. The

frequency will reach up to 51.2 Hz.
The difference between the current power frequency and P-HzStr (51.2 Hz ‒ 50.2 Hz) multiplied
by the gradient "P-WGra" (40%/Hz) results in an active power reduction of 40% in the last
available power P

cur

(350 kW). This results in a power limitation of 140 kW and a maximum active

power of 210 kW.
Calculation:
210 kW = 350 kW – ( (51.2 Hz – 50.2 Hz) * 40%/Hz * 350 kW)