10  Troubleshooting

Operating Manual

SCxxxHE-20-BE-BEN111210

75

05xx

Cause of error
The power frequency is not within the permissible range.
Error message 0502
< Grid frequency disturbance min >

– Power frequency is too low. Grid frequency from standard monitoring

detected.

Error message 0503
< Grid frequency disturbance max >

– Power frequency is too high. Grid frequency from standard monitoring

detected.

Error message 0504
< Grid frequency disturbance min >

– Power frequency is too low. Grid frequency disturbance from redundant

monitoring detected.

Error message 0505
< Grid frequency disturbance max >

– Power frequency is too high. Grid frequency disturbance from redundant

monitoring detected.

Measure
< Check power frequency >

– Check power frequency.
– Check the display of the grid monitoring relay.
– Check the fuses in the load circuit.

0801

Error message
< Grid failure >

– A power distribution grid phase has failed.

Measure
< Check grid fuses >

– Check the grid voltage.
– Make sure the external fuses are working properly.
– Make sure the AC cable is connected securely.