SMA SC 500HE-20 User Manual

Page 93

Advertising
background image

SMA Solar Technology AG

12  Parameters

Operating Manual

SCxxxHE-20-BE-BEN111210

93

PF-PFExtStr

**

Excitation of the
displacement
power factor cos φ
at characteristic
curve point 1

OvExt

Overexcited

OvExt

UnExt

Underexcited

PF-PFStop

**

Displacement
power factor cos φ
at characteristic
curve point 2,
The lower limit is
defined by
parameter
"PFAbsMin"

0.5 … 1

0.9

PF-PFExtStop

**

Excitation of the
displacement
power factor cos φ
at characteristic
curve point 2

OvExt

Overexcited

OvExt

UnExt

Underexcited

PF-WStr

**

Sets the feed-in
power in % at
characteristic curve
point 1

0% … 90%

0%

PF-WStop

**

Sets the feed-in
power in % at
characteristic curve
point 2.

10% … 100%

100%

Q-VDif

**

Voltage change
that causes a
change in reactive
power
Value corresponds
to rated voltage
VRtg

0.1% … 10%

1%

Q-VArGra

**

Change in reactive
power setpoint
during a voltage
step
Value corresponds
to the rated output
power Pmax

0% … 100%

1%

Name

Description

Value/Range

Explanation

Default

value