SMA SC 500HE-20 User Manual

Page 96

Advertising
background image

12  Parameters

SMA Solar Technology AG

96

SCxxxHE-20-BE-BEN111210

Operating Manual

VCtlllLimTm

*

Activation time for
undervoltage level 2

0 ms …

1 000 000 ms

country-

specific

VCtlMin

*

Threshold value for
undervoltage
activation level 3

0% … 100%

country-

specific

VCtlMinTm

*

Activation time for
undervoltage level 3

0 ms …

1 000 000 ms

country-

specific

VCtlPeakMax

*

Threshold value for
overvoltage

100% … 150%

country-

specific

VCtlPeakMaxTm

*

Activation time for
overvoltage

0 ms … 20 ms

country-

specific

VCtlOpMinNom

*

Minimal connection
voltage

0% … 100%

country-

specific

VCtlOpMaxNom

*

Maximum connection
voltage

100% … 200%

country-

specific

HzCtlOpMin

*

Minimum connection
frequency

country-specific

country-

specific

HzCtlOpMax

*

Maximum connection
frequency

country-specific

country-

specific

HzCtlMax

*

Threshold value for
overfrequency level 3

country-specific

country-

specific

HzCtlMaxTm

*

Activation time for
overfrequency level 3

0 ms …

1 000 000 ms

country-

specific

HzCtlhhLim

*

threshold value for
overfrequency level 2

country-specific

country-

specific

HzCtlhhLimTm

*

Activation time for
overfrequency level 2

0 ms …

1 000 000 ms

100 ms

HzCtlhLim

*

Threshold value for
overfrequency level 1

country-specific

country-

specific

HcCtlhLimTm

*

Activation time for
overfrequency level 1

0 ms …

1 000 000 ms

100 ms

HzCtllLim

*

Threshold value for
underfrequency
level 1

country-specific

country-

specific

HzCtllLimTm

*

Tripping time for
underfrequency
level 1

0 ms …

1 000 000 ms

100 ms

Name

Description

Range

Explanation

Default

value