10  Troubleshooting

Operating Manual

SCxxxHE-20-BE-BEN111210

77

35xx

Cause of error
A ground fault is present in the PV array.
Error message 3501
< Insulation Failure >
Error message 3502
< Ground fault >
Error message 3504
< Insulation failure ignored >
Error message 3505

< Ground fault ignored >

Error message 3507
< Soft grounding triggered >
Error message 3510
< Ground fault detected >
Error message 3512
< Permanent ground fault >
Error message 3515
< Soft grounding ignored >
Measure
< Check DC generator >

– Check the PV array for ground faults.

3601

Error message
< Warning insulation failure >

– There is leakage current at the grounding connection of the PV array.

Measure
< Check DC generator >

– Check the grounding connection and equipotential bonding.
– Check module wiring and plant design.

Error no.

Error message, cause of error and corrective measure