7 grid monitoring, 1 how grid monitoring works, 2 grid monitoring for grid voltage – SMA SC 500HE-20 User Manual

Page 57: Grid monitoring, How grid monitoring works, Grid monitoring for grid voltage

Advertising
background image

SMA Solar Technology AG

7  Grid Monitoring

Operating Manual

SCxxxHE-20-BE-BEN111210

57

7 Grid Monitoring

7.1 How Grid Monitoring Works

The Sunny Central monitors the power distribution grid to make sure it stays within a definable range
of limiting values. If these limiting values are exceeded for a set time period, the Sunny Central will
disconnect itself from the grid for safety reasons.
The following limiting values are monitored:

• Voltage loss protection
• Voltage increase protection
• Frequency loss protection
• Frequency increase protection

A tripping delay time for how long the grid failure must be present before the Sunny Central
disconnects from the grid can be set for each limiting value.

7.2 Grid Monitoring for Grid Voltage

Figure 22: Temporal behavior of the Sunny Central when exceeding the grid limits

Object Parameters

Description

A

VCtlhhLimTm

Delay time for grid limit level 2

B

VCtlhLimTm

Delay time for grid limit level 1

C

Startup/MPP load operation

D

Grid Monitoring

Advertising
This manual is related to the following products: