6  Setpoint for Active Power and Reactive Power

Operating Manual

SCxxxHE-20-BE-BEN111210

49

The analog value is converted to a target value for power limitation. Here, the "Pmax" parameter is
the end point of the linear characteristic curve.

Figure 15: Limiting the parameter "Pmax" to the parameter "Qmax"

If the value of "P

max

" exceeds the value of "Qmax", the characteristic curve for the value "Qmax" is

limited to "Qmax" and has a linear progression from -Pmax to − Q

max

and from +Q

max

to +P

max

.

Signal

Power limit

Description

< 2 mA

last valid value or 0 kVAr after

restart

Signal is in the invalid range.

2 mA … 4 mA

− Pmax

The maximum amount of negatively excited
reactive power is fed in.

4 mA

− Pmax

Start point of curve
Maximum amount of negatively excited
reactive power is fed in.

11.5 mA

0 kVAr

Zero-crossing of the curve
No reactive power is fed in.

> 19 mA

+Pmax

End point of the curve
Maximum amount of positively excited
reactive power is fed in.

Used parameters

None