12  Parameters

SMA Solar Technology AG

94

SCxxxHE-20-BE-BEN111210

Operating Manual

Q-VDifTm

**

Time span in which
the voltage change
must wait before the
reactive power
setpoint "Q-VArGra"
changes

0 s … 120 s

1 s

Q-VRtgOfsNom

**

Changes the rated
voltage "VRtg" of
the voltage-
dependent reactive
power controller
Parameter is active
only if parameter
"Q-VArMod" is set
to "VArCtlCol"

− 10% … +10%

0%

Q-VArGraNom

**

Reactive power
gradient

0%/V … 10%/V

0%/V

Q-VolWidNom

**

Voltage width

0% … 20%

0%

Q-VolNomP1

**

Voltage on point 1

0% … 20%

0%

Q-VolNomP2

**

Voltage on point 2

0% … 20%

0%

Q-VArTmsSpnt

**

Time setting of the
characteristic curve
point

1 s … 60 s

10 s

Q-VArTmsVtg

**

Delay of grid
voltage

1 s … 60 s

10 s

Q-EnaTmsVtg

**

Connection delay
of grid voltage

Off

Off

On

WGra

**

Gradient of active
power change

1% … 20%

20%

WGraEna

**

Activation of the
active power
change gradients

Off

Deactivated

Off

On

Activated

WGraReconEna

**

Activation of the
active power
increase ramp for
reconnection

Off

Deactivated

country-

specific

On

Activated

Name

Description

Value/Range

Explanation

Default

value