9 Main Command

28

YASKAWA ELECTRIC SIEP C730600 62B 1000-Series Option SI-ET3 Technical Manual

In the following status, an alarm is detected and the command goes into error.

Example: Writing C1-01 (200H)

‹

ID_RD: 03H (Read ID Command)

The ID_RD command is used to read the ID of a device. This command reads the product information as ID data.

2

CMD_STAT

Refer to

Command Status (CMD_STAT) on page 24

.

If the SIZE data is invalid, “9” is set for CMD_ALM.

3
4

NO

MEMOBUS/Modbus register number (Lower) set in the command.

5

MEMOBUS/Modbus register number (Upper) set in the command.

6

SIZE

The value set in the command.

7

Reserved (0)

0 is set.

8

PARAMETER

The value set in the command.
0 is stored when the field is not used.

9

10

x
x

31

Error

Response

Register Number Error

“9” is set for CMD_ALM.

Bit Count Error

“9” is set for CMD_ALM.

Data Setting Error

“9” is set for CMD_ALM.

Write Mode Error

“9” is set for CMD_ALM.

Writing Error during Under Voltage

“9” is set for CMD_ALM.

Writing Error during Parameter Processing

“9” is set for CMD_ALM.

Byte

Command

Response

4

00H

00H

5

02H

02H

6

02H

02H

7

00H

00H

8

Value set to C1-01 (Lower)

Value set to C1-01 (Lower)

9

Value set to C1-01 (Upper)

Value set to C1-01 (Upper)

ID_RD command

Byte

Command

Description

0

ID_RD (03H)

Command code

1

WDT

Watchdog data

2

CMD_CTRL

Refer to

Command Control (CMD_CTRL) on page 24

.

3

4

ID_CODE

Specifies the ID_CODE.
Refer to

Table 13

for details.

5

OFFSET

Set the offset in byte.

6

SIZE

Set the size in byte. (Lower)

7

Set the size in byte. (Upper)

8

Reserved (0)

Not used

x
x

31

PRM_WR Response

Byte

Response

Description