Yaskawa G7 Drive User Manual

Page 26

Advertising
background image

Date: 03/31/09, Rev: 09-03

Page 26 of 30

TM.G7SW.064


Figure 6 below shows an example of how a +12VDC current sinking (open collector NPN) sensor can be
used to trigger the marker pulse input (alignment input) of the encoder feedback card. An external power
supply may be required. For best noise immunity, locate the resistor network at the switch, not at the
encoder feedback card. Please note that the switch must be able to handle at least 22mA of current draw.
For exact application wiring, consult Yaskawa Application Engineering with the exact sensor specifications.

560 Ohm

1/2 Watt

Each

External

Alignment

Sensor

+12VDC Supply

OV Common

Z+ Marker Pulse Input

Z- Marker Pulse Input

Power Supply

Encoder Feedback Card

+

-

Twisted Pair

Twisted Pair

Use 4-wire cable with 2 twisted

pairs and 1 overall shield.

Figure 6: Wiring Example of External Alignment Sensor


Advertising
This manual is related to the following products: