Yaskawa YASNAC PC NC PLC Programming Manual User Manual
Page 122

6 - 86
YASNAC PCNC PLC Programming Manual Chapter 6: PLC Instructions
(c) Control conditions
•
Designation of the multiplicand data address (APSH#XXXX)
Designate the address where the multiplicand data is stored.
•
Designation of the multiplier data address (APSH/IPSHD#XXXX)
Designate the address where the multiplier data is stored.
•
Designation of the operation result output address (APSH#XXXX)
Designate the address where the result of operation is output.
The address is stored as 4-byte data.
•
Designation of the type of operation (IPSH X).
Designate the data length and the data type of multiplicand/multiplier.
1st digit
= 0: 1byte
= 1: 2 bytes
= 2: 4bytes
2nd digit
= 0: Constant data
= 1: Address data
•
Execution command (ACT)
ACT = 0: The binary-data multiplication instruction is executed.
R1 remains unchanged.
ACT = 1: The binary-data multiplication instruction is not executed.
•
Error output (OUT)
OUT = 0: Normal
OUT = 1: Error
•
#2999
Operation status is written.
d0 = 1:
0
d1 = 1:
Negative
d5 = 1:
Overflow