Yaskawa YASNAC PC NC PLC Programming Manual User Manual

Page 93

Advertising
background image

6 - 57

YASNAC PCNC PLC Programming Manual Chapter 6: PLC Instructions

Designate the address where the data, stored at the number in the table which is
specified in item 2 above, should be output.

If “BYT = 1”, the upper byte data are output to the address next to the designated
address.

Designation of the conversion data table (TPSHXXXX)

The size of table differs depending on the PLC table number.

9000 to 9007: Max 256 bytes

9008 to 9023: Max. 128 bytes

Designation of the data size (BYT)

Designate the size of the data in the conversion data table.

BYT = 0: 1 byte

BYT = 1: 2 bytes

Reset (RST)

Designate whether or not the error output coil R1 is reset.

RST = 0: Not reset

RST = 1: Reset

Execution command (ACT)

ACT = 0: The COD instruction is not executed. R1 remains unchanged.

ACT = 1: The COD instruction is executed.

Error output (R1)

If an error occurs during the execution of the COD instruction (a numeric value
greater that the size of the table is set), “1” is set for “R1” (R1” (R1 = 1) indicating
the occurrence of an error.

Advertising