6 - 40

YASNAC PCNC PLC Programming Manual Chapter 6: PLC Instructions

(33)CMRW (Complement Word Register) RR after operation: RR-

(a) Function

The instruction reverses the content of double-length register when the ST content is ON
(RR = 1)

(b) Format

(c) Explanation

•

A ST contact must be entered before the CMRW instruction.

•

The CMRW instruction is executed in intervals of “4 × n” msec while the ST contact
is ON.

•

There is no function to detect underflow. If the result of operation exceeds 0H, it
returns to FFFH.

(34)CORW (Coincide Word Register) RR after operation: RR

Ù

(a) Function

The instruction executes comparison between WR1 and WR2 when the ST content is
ON (RR = 1), and sets “0” or ”1” to Z1 according to the result of comparison.

WR1 = WR2 Z1= 1

WR

≠

WR2 Z1 = 0

If the ST contact is OFF (RR = 0), the CORW instruction is not executed.The content
of RR remains unchanged.

(b) Format

(c) Explanation

•

After the execution of CORW instruction, the contents of WR1 and WR2 remain
unchanged.

•

A ST contact must be entered before the CORW instruction.

•

The CORW instruction is executed in intervals of “4 × n” msec while the ST contact
is ON.

D