2.4 Cable Specifications and Peripheral Devices

24

2.4 Cable Specifications and Peripheral Devices

Ratings and specifications for peripheral devices, as well as cable specifications for digital
torque amplifiers are summarized in the tables below.

Cable Specifications

Notes:

1.

Wire sizes were selected for three cables per bundle at 40°C ambient temperature with the rated current.

2.

Use cables with a minimum withstand voltage of 600V for main circuits.

3.

If cables are bundled in PVC or metal ducts, consider the reduction ratio of the allowable current.

4.

Use heat-resistant cable under high ambient or panel temperatures where normal vinyl cable will rapidly
deteriorate.

External Terminal Name

SGDG

Terminal

Symbol

Wire Size AWG [in

2

(mm

2

)]

01GT

04GT

Main circuit power input terminals

L1, L2
(Single Phase)

16 AWG [HIV 0.002

(1.25)]

14 AWG [0.003 (2.0)]

Servomotor connection terminals

U, V, W

16 AWG [HIV 0.002 (1.25)]

Control power supply terminals

L1C, L2C

Control I\O signal connector

CN1

Twisted pair or shielded twisted pair wires
Core wire at least 28 AWG [0.0002

(0.12)], tinned,

annealed copper twisted wires
Finished cable dimensions:
maximum

Φ

0.63in (16mm) for CN1 and

Φ

0.27in

(6.8mm) for CN2.

PG signal connector

CN2

Ground terminal

14 AWG [HIV 0.003 (2.0)]

Main circuit power input terminals

L1, L2, L3
(Three-phase)

14 AWG [HIV 0.003 (2.0)]

Servomotor connection terminals

U, V, W

Control power supply terminals

L1C, L2C

16 AWG [HIV 0.002 (1.25)]

Control I\O signal connector

CN1

Twisted pair or shielded twisted pair wires

Core wire at least 28 AWG [0.0002

(0.12)], tinned,

annealed copper twisted wires
Finished cable dimensions: maximum

Φ0.63in

(16mm) for CN1 and

Φ0.27in (6.8mm) for CN2.

PG signal connector

CN2

Ground terminal

14 AWG [HIV 0.003 (2.0)]

Wiring Precautions

Do not bundle or run power and signal lines together in the same duct.

Keep power and signal lines at least 11.81” (30cm) apart.

Use twisted pair or shielded multi-core twisted pair wires for signal and
encoder (PG) feedback lines.

The maximum lengths for signal lines are as follows:

Maximum of 9.84ft (300cm) for reference input lines.

Maximum of 65.6ft (20m) for PG feedback lines.

Use a cable with 164 ft (50m) specifications for distances over 65.6ft (20m).