Safety Notes

In this manual, we will describe important cautionary items which should always be
observed regarding usage, inspection upon receipt of product, mounting, wiring,
operation, and maintenance/inspection.

Inspection Upon Receipt of Product

Mounting

Wiring

• Use the servomotors and amplifiers in the designated combinations. (

See “3.5

Combinations” on page 39.

)

Failure to do so may result in fire or unit failure.

• Never use this product in an area where water may splash, in a corrosive or flammable

atmosphere, or next to flammable items.

Doing so may result in electric shock or fire.

• Be sure to connect the ground terminal of the digital torque amplifier to a grounding

electrode (100

Ω or less).

Failure to do so may result in electric shock or fire.

Wiring Precautions

• Do not bundle or run power and signal lines together in the same duct.

Keep power and signal lines at least 11.81” (30cm) apart.

• Use twisted pair or shielded multi-core twisted pair wires for signal and encoder (PG)

feedback lines.

• The maximum lengths for signal lines are as follows:

• Maximum of 9.84ft (300cm) for reference input lines.

• Maximum of 65.6ft (20m) for PG feedback lines.

• Use a cable type UL20276-SB for distances over 65.6ft (20m).