background image

5 Electrical Installation

20

YASKAWA TOEP YAIL1E 02A YASKAWA AC Drive - L1000E Safety Precautions

Note: When connecting peripheral devices and options to the terminals –, +1, +3, B1, and B2, refer to the instruction manuals for each

device. For more information, contact Yaskawa or your nearest sales representative.

2A0225

R/L1, S/L2, T/L3

70

× 2P

(1/0

× 2P)

70 to 95

(1/0 to 4/0)

M10

18 to 23

(159 to 204)

U/T1, V/T2, W/T3

70

× 2P

(1/0

× 2P)

70 to 95

(1/0 to 4/0)

–, +1

50 to 95

(1 to 4/0)

+3

70 to 95

(1/0 to 4/0)

25

(4)

25 to 50

(4 to 1/0)

2A0269

R/L1, S/L2, T/L3

95

× 2P

(3/0

× 2P)

95 to 150

(3/0 to 300)

M12

32 to 40

(283 to 354)

U/T1, V/T2, W/T3

95

× 2P

(3/0

× 2P)

95 to 150

(3/0 to 300)

–, +1

95 to 150

(3/0 to 300)

+3

35 to 150

(2 to 300)

M10

18 to 23

(159 to 204)

35

(3)

35 to 150

(2 to 300)

M12

32 to 40

(283 to 354)

2A0354

R/L1, S/L2, T/L3

120

× 2P

(4/0

× 2P)

95 to 150

(3/0 to 300)

M12

32 to 40

(283 to 354)

U/T1, V/T2, W/T3

120

× 2P

(4/0

× 2P)

95 to 150

(3/0 to 300)

–, +1

95 to 150

(3/0 to 300)

+3

95 to 150

(3/0 to 300)

M10

18 to 23

(159 to 204)

35

(2)

35 to 150

(2 to 300)

M12

32 to 40

(283 to 354)

2A0432

R/L1, S/L2, T/L3

150

× 2P

(250

× 2P)

95 to 300

(4/0 to 600)

M12

32 to 40

(283 to 354)

U/T1, V/T2, W/T3

185

× 2P

(300

× 2P)

95 to 300

(4/0 to 600)

–, +1

120 to 300

(250 to 600)

+3

70 to 300

(3/0 to 600)

M10

18 to 23

(159 to 204)

50

(1)

120 to 240

(1 to 350)

M12

32 to 40

(283 to 354)

Drive Model

Terminal

Recommended

Wire Size

mm

2

(AWG, kcmil)

Wire Range

mm

2

(AWG, kcmil)

Screw

Size

Tightening Torque

N•m (lb.in.)