Serial communication terminals – Yaskawa AC Drive-L1000E Safety Precautions User Manual

Page 30

Advertising
background image

5 Electrical Installation

30

YASKAWA TOEP YAIL1E 02A YASKAWA AC Drive - L1000E Safety Precautions

„

Serial Communication Terminals

Table 11 Control Circuit Terminals: Serial Communications

MEMOBUS/Modbus Termination

This drive is equipped with a built-in termination resistor for the RS-422/485 communication port. DIP switch S2 enables
or disables the termination resistor as shown in

Figure 11

. The OFF position is the default. The termination resistor

should be placed to the ON position when the drive is the last in a series of slave drives.

Table 12 MEMOBUS/Modbus Switch Settings

Figure 11

Figure 11 DIP Switch S2

„

Control Circuit Wire Size and Torque Specifications

WARNING! Fire hazard. Tighten all terminal screws to the specified tightening torque. Loose electrical connections could result in

death or serious injury by fire due to overheating of electrical connections. Improperly tightened terminal screws can also cause

erroneous equipment operation.

Select appropriate wire type and gauges from

Table 13

. For simpler and more reliable wiring, use crimp ferrules on the

wire ends.

Table 13 Wire Gauges and Torque Specifications

Type

<1> Enable the termination resistor in the last drive in a MEMOBUS network by setting DIP switch S2 to the ON position.

No.

Signal Name

Function (Signal Level)

MEMOBUS/Modbus
Communication

<1>

R+

Communications input (+)

MEMOBUS/Modbus communication: Use
an RS-485 or RS-422 cable to connect the
drive.

RS-485/422
MEMOBUS/Modbus
communication
protocol
115.2 kbps (max.)

R-

Communications input (-)

S+

Communications output (+)

S-

Communications output (-)

IG

Shield ground

0 V

S2 Position

Description

ON

Internal termination resistor ON

OFF

Internal termination resistor OFF (default setting)

Terminal

Block

Terminal

Size

Tightening

Torque

N•m

(lb.in.)

Bare Wire Terminal

Ferrule-Type Terminal

Applicable

Wire Size

mm

2

(AWG)

Recomm.

mm

2

(AWG)

Applicable

Wire Size

mm

2

(AWG)

Recomm.

mm

2

(AWG)

Wire Type

TB1, TB2,
TB4, TB5,

TB6

FM, AC, AM, P1,

P2, PC, SC, A1,

A2, A3, +V, -V, S1-

S8, MA, MB, MC,

M1, M2, HC, H1,

H2, DM+, DM-, IG,

R+, R-, S+, S-, RP,

MP, E (G)

M2

0.22 to 0.25

(1.9 to 2.2)

Standard wire:

0.25 to 1.0

(24 to 17)

Solid wire:

0.25 to 1.5

(24 to 16)

0.75

(18)

0.25 to 0.5

(24 to 20)

0.5

(20)

Shielded wire,

etc.

DIP Switch S2

(OFF:default)

OFF

ON

Advertising