5 Electrical Installation

YASKAWA TOEP YAIL1E 02A YASKAWA AC Drive - L1000E Safety Precautions

29

„

Output Terminals

Table 10

lists the output terminals on the drive. Text in parenthesis indicates the default setting for each multi-function

output.

Note: Multi-function relay output terminals are rated at a minimum of 10 mA. If less than 10 mA is required, use the photocoupler

outputs (P1-C1, P2-C2). Using the wrong current output level may cause the output to malfunction when the terminal is activated.

Table 10 Control Circuit Output Terminals

Figure 10

Figure 10 Connecting a Suppression Diode

H4-07, H4-08: Terminal FM, AM Signal Level Selection

Sets the voltage output level of U parameter (monitor parameter) data to terminal FM and terminal AM using parameters
H4-07 and H4-08.

Setting 0: 0 to 10 V

Setting 1: -10 V to 10 V

Type

<1> Refrain from assigning functions to terminals M1 thru M6 that involve frequent switching, as doing so may shorten relay performance life.

Switching life is estimated at 200,000 times (assumes 1 A, resistive load).

<2> Connect a suppression diode as shown in

Figure 10

when driving a reactive load such as a relay coil. Make sure the diode rating is greater than

the circuit voltage.

No.

Terminal Name (Function)

Function (Signal Level) Default Setting

Fault Relay

MA

N.O.

30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A
Minimum load: 5 Vdc, 10 mA

MB

N.C. output

MC

Fault output common

Multi-Function
Relay Output

<1>

M1

Multi-function relay output 1 (Brake release
command)

Contact relay output
30 Vdc, 10 mA to 1 A
250 Vac, 10 mA to 1 A
Minimum load: 5 Vdc, 10 mA

M2
M3

Multi-function relay output 2 (Output contactor close
command)

M4
M5

Multi-function relay output 3 (Drive ready)

M6

Multi-Function
Photocoupler
Output

P1

Photocoupler output 1 (During Frequency output)

48 Vdc, 2 to 50 mA

<2>

C1

P2

Photocoupler output 2 (Not Used/Through Mode)

C2

Monitor Output

FM

Analog monitor output 1 (Output speed)

-10 to +10 Vdc or 0 to +10 Vdc

AM

Analog monitor output 2 (Output current)

AC

Monitor common

0 V

Safety Monitor
Output

DM+ Safety monitor output

Outputs status of Safe Disable function. Closed when both Safe
Disable channels are closed. Up to +48 Vdc 50 mA

DM-

Safety monitor output common

A – External power, 48 V max.

C – Coil

B – Suppression diode

D – 50 mA or less

No.

Parameter Name

Setting Range

Default

H4-07

Terminal FM Signal Level Selection

0 or 1

0

H4-08

Terminal AM Signal Level Selection

0 or 1

0

A

B

C

D