8 Troubleshooting

YASKAWA TOEP YAIL1E 02A YASKAWA AC Drive - L1000E Safety Precautions

37

BB,HBB

bb

O

Baseblock
Drive output interrupted as indicated by an external baseblock signal.

Hbb

O

Safe Disable Circuit Fault Signal (H1-HC, H2-HC) Release
Both Safe Disable Input channels are open.

HbbF

O

Safe Disable Circuit Fault Signal (H1-HC, H2-HC) Release
One Safe Disable channel is open while the other one is closed.

ALARM(RUN)

OV,UV

ov

O

O

DC Bus Overvoltage
Voltage in the DC bus has exceeded the overvoltage detection level.

• For 200 V class: approximately 410 V
• For 400 V class: approximately 820 V

Uv1

O

DC Bus Undervoltage
One of the following conditions occurred while the drive was running:

• Voltage in the DC bus fell below the undervoltage detection level (L2-05)
• For 200 V class: approximately 190 V
• For 400 V class: approximately 380 V (350 V when E1-01 is less than 400)

Uv2

O

Control Power Supply Voltage Fault
Voltage is too low for the control drive input power.

Uv3

O

Soft-Charge Bypass Circuit Fault
The soft-charge bypass circuit failed.

ALARM(RUN)

OH,OL

oH

O

O

Heatsink Overheat
The temperature of the heatsink exceeded the overheat pre-alarm level set to L8-02 (90-
100

°C). Default value for L8-02 is determined by drive capacity (o2-04).

OH,OL

oH1

O

Heatsink Overheat
The temperature of the heatsink exceeded the drive overheat level. The overheat level is
determined by drive capacity (o2-04).

ALARM(RUN)

OH,OL

oH3

O

O

Motor Overheat Alarm (PTC thermistor input)

• The motor overheat signal to analog input terminal A1 or A2 exceeded the alarm

detection level.

• Detection requires multi-function analog input H3-02 or H3-10 be set to “E”.

OH,OL

oH4

O

Motor Overheat Fault (PTC thermistor input)

• The motor overheat signal to analog input terminal A1 or A2 exceeded the fault detection

level.

• Detection requires that multi-function analog input H3-02 or H3-10 = “E”.

oL1

O

Motor Overload
The electronic motor overload protection tripped.

oL2

O

Drive Overload
The thermal sensor of the drive triggered overload protection.

ALARM(RUN)

OH,OL

oL3

O

O

Overtorque Detection 1
Drive output current (or torque in OLV, CLV, CLV/PM) was greater than L6-02 for longer
than the time set in L6-03.

oL4

O

O

Overtorque Detection 2
Drive output current (or torque in OLV, CLV, CLV/PM) was greater than L6-05 for longer
than the time set in L6-06.

OC,GF,SC,PGO

GF

O

Ground Fault
A current short to ground exceeded 50% of rated current on the output side of the drive.

oC

O

Overcurrent
Drive sensors have detected an output current greater than the specified overcurrent level.

PGOH,LT

OC,GF,SC,PGO

PGo

O

O

Encoder Disconnected (for Control Mode with Encoder)
Detected when no encoder signal is received for a time longer than setting in F1-14.

PGoH

O

O

Encoder Disconnected (detected when using an encoder)
Encoder cable has become disconnected.

JVOP-184