4A0114

R/L1, S/L2, T/L3

70

(1/0)

16 to 120

(6 to 250)

M8

9 to 11

(79.7 to 97.4)

U/T1, V/T2, W/T3

70

(1/0)

16 to 120

(6 to 250)

–, +1

25 to 50

(3 to 1/0)

+3

25 to 50

(4 to 1/0)

25

(4)

16 to 25

(6 to 4)

4A0140

R/L1, S/L2, T/L3

95

(3/0)

50 to 95

(1/0 to 4/0)

M10

18 to 23

(159 to 204)

U/T1, V/T2, W/T3

70

(2/0)

50 to 95

(1/0 to 4/0)

–, +1

50 to 95

(1/0 to 4/0)

+3

25 to 95

(3 to 4/0)

25

(4)

25

(4)

4A0188

R/L1, S/L2, T/L3

95

(4/0)

50 to 95

(1/0 to 4/0)

M10

18 to 23

(159 to 204)

U/T1, V/T2, W/T3

95

(4/0)

50 to 95

(1/0 to 4/0)

–, +1

35 to 95

(1 to 4/0)

+3

50 to 95

(1/0 to 4/0)

25

(4)

25 to 35

(4 to 2)

4A0225

R/L1, S/L2, T/L3

50

× 2P

(1

× 2P)

35 to 150

(2 to 300)

M10

18 to 23

(159 to 204)

U/T1, V/T2, W/T3

70

× 2P

(1/0

× 2P)

35 to 150

(2 to 300)

–, +1

50 to 150

(1 to 250)

+3

25 to 70

(3 to 3/0)

25

(4)

25 to 150

(4 to 300)

4A0260

R/L1, S/L2, T/L3

70

× 2P

(2/0

× 2P)

95 to 300

(1 to 600)

M10

18 to 23

(159 to 204)

U/T1, V/T2, W/T3

70

× 2P

(2/0

× 2P)

95 to 300

(1/0 to 600)

–, +1

70 to 300

(3/0 to 600)

+3

35 to 185

(1 to 325)

35

(2)

35 to 185

(2 to 350)

Drive Model

Terminal

Recomm. Gauge

AWG, kcmil

Wire Range

AWG, kcmil

Screw

Size

Tightening Torque

N•m (lb.in.)

Advertising